Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 01/18/2013 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection :* |
| 11/28/2012 |
MECHANICAL - FINAL |
|
Not ready for Inspection |
DUCT EXPOSED TO EXTERIOR IS TO HAVE A MINIMUM R-VALUE RATING OF 8 (2" LINER) 1" LINER ONLY PROVIDES A 4-2 RATING. CONDENSATE TO HAVE P-TRAP PER INSTALLATION INSTRUCTIONS. T-STAT WIRE IS TO BE INSTALLED IN PROTECTING CONDUIT WHEN EXPOSED TO EXTERIOR. |