Permit: T08CM01924

Parcel: 12411032A


Addresses:

1824 E 12TH ST #01

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
01/18/2013 MECHANICAL - FINAL Approved IVRS - Inspection :*
11/28/2012 MECHANICAL - FINAL Not ready for Inspection DUCT EXPOSED TO EXTERIOR IS TO HAVE A MINIMUM R-VALUE RATING OF 8 (2" LINER) 1" LINER ONLY PROVIDES A 4-2 RATING. CONDENSATE TO HAVE P-TRAP PER INSTALLATION INSTRUCTIONS. T-STAT WIRE IS TO BE INSTALLED IN PROTECTING CONDUIT WHEN EXPOSED TO EXTERIOR.