Permit: T08CM01924

Parcel: 12411032A


Addresses:

1824 E 12TH ST #01

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
08/27/2012 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
08/24/2012 MECHANICAL - INTERMEDIATE Partial Approval ITEM 4 NOT CORRECTED
08/09/2012 MECHANICAL - INTERMEDIATE Denied 1) DUCT NOT SIZED PER PLAN
2) ALL EXTERIOR DUCT OT HAVE AN R-VALVE OF 8MIN.
3) BUBBLE WRAP INSULATION NOT INSTALLED CORRECTLY PROVIDE INSTALLATION INSTRUCTIONS.
4) DRYER VENTING INSTALLED BACKWARDS
5) BOOT BOXES ARE TO BE FRAMED ON 3 SIDES MIN.
6) COMPLETE INSTALLATION IN SOFFIT