Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T08CM01820
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/15/2009 | PLUMBING - FINAL | Approved | IVRS - Inspection :* RECEIVED CHLORINE & BACTERIA REPORT |
|
01/13/2009 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* SEAL INSULATION PROPERLY AND SEE NOTE #1 FROM 1/9/09 INSPECTION |
|
01/12/2009 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
01/09/2009 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. PROVIDE CHLORINE REPORT AND BACTERIA REPORT FOR POTABLE WATER SUPPLY 2. PER 2006 UPC REQUIREMENTS ELEVATED WATER HEATER ABOVE FIXTURES IS REQUIRED TO HAVE A VACUUM RELIEF DEVICE ON THE WATER HEATER PIPING 3. COMMERCIAL BUILDINGS REQUIRE OPEN FRONT SEATS ON STOOLS 4. MOP SINK TO BE MADE WATER TIGHT AT FLOOR 5. T&P DRAIN TO HAVE 1" AIR GAP AT TERMINATION 6. INSULATE HOT & COLD PIPING PER 2006 INTERNATIONAL ENERGY CONSERVATION CODE REQUIREMENT 7. CALL IN ALL INSPECTIONS FOR PLUMBING THAT HAVE NOT BEEN APPROVED 8. CLEANOUT PLUGS ARE TO BE FACTORY TAPPED AND CLEANOUT COVERS ATTACH WITH MACHINE SCREWS 9. THE VENT ON THE BACKFLOW DEVICE CANNOT BE PLUGGED OR DISCHARGE ONTO AN ELECTRICAL OUTLET RECEIVED OK FOR 2" |