Permit: T08CM01820

Parcel: 12801005H

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T08CM01820

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/15/2009 PLUMBING - FINAL Approved IVRS - Inspection :*
RECEIVED CHLORINE & BACTERIA REPORT
01/13/2009 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
SEAL INSULATION PROPERLY AND SEE NOTE #1 FROM 1/9/09 INSPECTION
01/12/2009 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
01/09/2009 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. PROVIDE CHLORINE REPORT AND BACTERIA REPORT FOR POTABLE WATER SUPPLY
2. PER 2006 UPC REQUIREMENTS ELEVATED WATER HEATER ABOVE FIXTURES IS REQUIRED TO HAVE A VACUUM RELIEF DEVICE ON THE WATER HEATER PIPING
3. COMMERCIAL BUILDINGS REQUIRE OPEN FRONT
SEATS ON STOOLS
4. MOP SINK TO BE MADE WATER TIGHT AT FLOOR
5. T&P DRAIN TO HAVE 1" AIR GAP AT TERMINATION
6. INSULATE HOT & COLD PIPING PER 2006 INTERNATIONAL ENERGY CONSERVATION CODE REQUIREMENT
7. CALL IN ALL INSPECTIONS FOR PLUMBING THAT HAVE NOT BEEN APPROVED
8. CLEANOUT PLUGS ARE TO BE FACTORY TAPPED AND CLEANOUT COVERS ATTACH WITH MACHINE SCREWS
9. THE VENT ON THE BACKFLOW DEVICE CANNOT BE PLUGGED OR DISCHARGE ONTO AN ELECTRICAL OUTLET

RECEIVED OK FOR 2"