Permit: T08CM01820

Parcel: 12801005H

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T08CM01820

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/26/2009 ELECTRIC - FINAL Approved
01/16/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. ROOFTOP ITEMS CORRECTED
2. RECALL WHEN NEW LIGHT FIXTURES ARE ON SITE
01/14/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. AC UNIT ON ROOF OVERFUSED. MARK NAME PLATE
2. NEED TO GROUND SAT. DISH
3. RECALL WHEN NEW LIGHT FIXTURES ARE ON SITE
01/12/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. LIGHT FIXTURE @ ENTRY TO BE GROUNDED CHECK ALL FIXTURES
2. BOXES TO BE FLUSH WITH COMBUSTIBLE MATERIAL
3. CANNOT USE DRYWALL SCREWS FOR CONNECTION OF GROUND BAR
4. CANNOT CONNECT GEC TO BUILDING STEEL WITH BEAM CLAMP
5. BOND WATER PIPING
6. INSTALL ARC FLASH WARNING LABEL
7. NEED TO CHECK ROOF NEXT INSPECTION