Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/26/2009 | ELECTRIC - FINAL | Approved | ||
| 01/16/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. ROOFTOP ITEMS CORRECTED 2. RECALL WHEN NEW LIGHT FIXTURES ARE ON SITE |
|
| 01/14/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. AC UNIT ON ROOF OVERFUSED. MARK NAME PLATE 2. NEED TO GROUND SAT. DISH 3. RECALL WHEN NEW LIGHT FIXTURES ARE ON SITE |
|
| 01/12/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. LIGHT FIXTURE @ ENTRY TO BE GROUNDED CHECK ALL FIXTURES 2. BOXES TO BE FLUSH WITH COMBUSTIBLE MATERIAL 3. CANNOT USE DRYWALL SCREWS FOR CONNECTION OF GROUND BAR 4. CANNOT CONNECT GEC TO BUILDING STEEL WITH BEAM CLAMP 5. BOND WATER PIPING 6. INSTALL ARC FLASH WARNING LABEL 7. NEED TO CHECK ROOF NEXT INSPECTION |