Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T08CM01820
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/14/2009 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
01/12/2009 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
01/07/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. OK CEILINGS 2. TRACK LIGHTING NOT TO BE CORD AND PLUG CONNECTED SEE NEC 410.101 |
|
12/31/2008 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) VDV CABELING TO BE SUPPORTED PER 725.24, 760.24, 800.24 & 300.11 2) SUPPORT WIRES NEEDED FOR EXIT LIGHTS, STRIP FLOURESCENTS 3) BOXES OVER FILLED 4) SUPPORT M/C CABLE 12" X 6' FT AND OFF OF GRID 5) FILL UNUSED OPENINGS IN BOX 6) CORDS NOT ALLOWED ABOVE CEILINGS 400.7 & 8 |
|
12/11/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK REMAINDER OF HARD LIDS |
|
12/05/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* |