Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/12/2008 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* DRAIN PAN MUST BE MIN. 1 1/2" LARGER THAN FAN COIL. OK FOR CEILING TILES. LEAVE OUT AROUND FAN COIL. |
|
| 09/10/2008 | MECHANICAL - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. TAPE IS NOT INSULATION, INSULATE DUCT AS REQUIRED BY PLANS, SPECS, CODE 2. FLEX NOT TO EXCEED 5' 3. ALL TAPS ARE TO BE HIGH EFFICIENCY PER PLANS, NO STRAIGHT TAPS 4. SEAL ALL VAPOR BARRIERS 5. PROVIDE SHEETMETAL 90 DEG. ELBOWS ON GRILLS PER PLAN OR PROPER RADIUS ON FLEX 6. REPAIR CONDENSATE INSULATION 7. PROVIDE FILTERS AT O.S.A 8. PROVIDE FLEXES AT UNITS AND PROPERLY INSTALL ISOLATORS |