Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/29/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 09/26/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* OUTSIDE EM LIGHTS NOT WORKING |
|
| 09/25/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* COMPLETE OUTSIDE EM LIGHTING INSTALL |
|
| 09/17/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. INSTALL SERVICE RECEPTACLE FOR CONDENSING UNIT 2. INSTALL WORK STATIONS 3. EM LIGHTING IN WAREHOUSE TO MEET REQUIREMENTS OF 700.15 EM LIGHTING IN WAREHOUSE TO BE POWERED FROM SAME PANEL BOARD AS NORMAL LIGHTING NEC 700.12(F) 4. INSTALL SINGLE POLE BREAKERS FOR 277V LIGHTING WAREHOUSE 5. NEED REVISION TO PLANS FOR CHANGES |