Permit: T08CM01727

Parcel: 141085300

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
09/29/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
09/26/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
OUTSIDE EM LIGHTS NOT WORKING
09/25/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
COMPLETE OUTSIDE EM LIGHTING INSTALL
09/17/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. INSTALL SERVICE RECEPTACLE FOR CONDENSING UNIT
2. INSTALL WORK STATIONS
3. EM LIGHTING IN WAREHOUSE TO MEET REQUIREMENTS OF 700.15 EM LIGHTING IN WAREHOUSE TO BE POWERED FROM SAME PANEL BOARD AS NORMAL LIGHTING NEC 700.12(F)
4. INSTALL SINGLE POLE BREAKERS FOR 277V LIGHTING WAREHOUSE
5. NEED REVISION TO PLANS FOR CHANGES