Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T08CM01713
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/14/2008 | PLUMBING - FINAL | Approved | IVRS - Inspection :* RECEIVED BACTERIA REPORT FOR POTABLE WATER |
|
07/07/2008 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PER ROBERT SHERRY I.W RECEPTACLE ABOVE CEILING OK 2. ONLY ONE SLIP NUT ALLOWED ON THE OUTLET SIDE OF THE TRAP 3. ALL HOT WATER PIPING TO BE INSULATED 4. PROVIDE CLEAN BACTERIA REPORT. IS IT SAFE TO HAVE PERSONNEL IN THE BLDG. BEFORE YOU KNOW IF THE WATER IS SAFE? 609.9 2006 UPC YOU DO NOT HAVE PERMISSION TO OCCUPY |
|
07/03/2008 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* - SEE NOTE NUMBER 3 FROM 05/30/08 - I BELIEVE THE ABOVE CEILING INDIRECT WASTE RECEPTOR HAS A HIGH POTENTIAL TO CREATE AN UNSANITARY CONDITION - TRAP PRIMERS ARE NOTORIOUS FOR FAILING AND CONDENSATE WASTE IS INTERMITTENT AND SEASONAL, LEAVING A DRY TRAP IN A CLOSED AREA - LAVATORIES REQUIRE MIXING VALVES - SEE P1 PLBG. FIX. SCH. P-2 LAVATORY |