Permit: T08CM01713

Parcel: 125081150

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T08CM01713

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/14/2008 PLUMBING - FINAL Approved IVRS - Inspection :*
RECEIVED BACTERIA REPORT FOR POTABLE WATER
07/07/2008 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PER ROBERT SHERRY I.W RECEPTACLE ABOVE CEILING OK
2. ONLY ONE SLIP NUT ALLOWED ON THE OUTLET SIDE OF THE TRAP
3. ALL HOT WATER PIPING TO BE INSULATED
4. PROVIDE CLEAN BACTERIA REPORT. IS IT SAFE TO HAVE PERSONNEL IN THE BLDG. BEFORE YOU KNOW IF THE WATER IS SAFE? 609.9 2006 UPC
YOU DO NOT HAVE PERMISSION TO OCCUPY
07/03/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
- SEE NOTE NUMBER 3 FROM 05/30/08
- I BELIEVE THE ABOVE CEILING INDIRECT WASTE RECEPTOR HAS A HIGH POTENTIAL TO CREATE AN UNSANITARY CONDITION
- TRAP PRIMERS ARE NOTORIOUS FOR FAILING AND CONDENSATE WASTE IS INTERMITTENT AND SEASONAL, LEAVING A DRY TRAP IN A CLOSED AREA

- LAVATORIES REQUIRE MIXING VALVES - SEE P1 PLBG. FIX. SCH. P-2 LAVATORY