Permit: T08CM01713

Parcel: 125081150

Inspection Status: Not ready for Inspection

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T08CM01713

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Not ready for Inspection

Date Description Inspector Results Comments
06/26/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. CLOSE OFF ALL CEILING J-BOXES
2. REMOVE ALL LOW VOLTAGE WIRING BACK TO SOURCE

OK TO INSTALL CEILING TILES
06/20/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
06/18/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. USE WIRE NUTS AS LISTED - 110.3
2. DEMO CEILING
3. USE GROUND SCREWS - NOT CLIPS - 250
4. MAX/EXTENSION BOX (314.16) - CHECK BOX FILL
5. SUPPORT WIRING OFF GRID
06/06/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALL COVER
05/30/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. HAVE SEVERAL LOOSE GROUNDS UNDER GROUND SCREWS IN J-BOXES
2. NEED NAIL PLATES FOR MC WHERE HOLE IS LESS
THAN 1 1/4 FROM STUD FACE
3. EXISTING RECEPTACLES NOT TO BE BURIED BEHIND WALLS
4. MC TO BE SECURED WITHIN 12" OF TERMINATIONS
5. PLANS TO BE REVISED TO SHOW SINGLE LINE DIAGRAM, PANELS (S) THAT WILL SUPPLY NEW LOADS AND HOME RUNS FEEDING NEW LOADS