Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Not ready for Inspection
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T08CM01713
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Not ready for Inspection
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/26/2008 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. CLOSE OFF ALL CEILING J-BOXES 2. REMOVE ALL LOW VOLTAGE WIRING BACK TO SOURCE OK TO INSTALL CEILING TILES |
|
06/20/2008 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
06/18/2008 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. USE WIRE NUTS AS LISTED - 110.3 2. DEMO CEILING 3. USE GROUND SCREWS - NOT CLIPS - 250 4. MAX/EXTENSION BOX (314.16) - CHECK BOX FILL 5. SUPPORT WIRING OFF GRID |
|
06/06/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALL COVER |
|
05/30/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. HAVE SEVERAL LOOSE GROUNDS UNDER GROUND SCREWS IN J-BOXES 2. NEED NAIL PLATES FOR MC WHERE HOLE IS LESS THAN 1 1/4 FROM STUD FACE 3. EXISTING RECEPTACLES NOT TO BE BURIED BEHIND WALLS 4. MC TO BE SECURED WITHIN 12" OF TERMINATIONS 5. PLANS TO BE REVISED TO SHOW SINGLE LINE DIAGRAM, PANELS (S) THAT WILL SUPPLY NEW LOADS AND HOME RUNS FEEDING NEW LOADS PRESIDIO MGMT JUAN NGO GEN 271-1348 |