Permit: T08CM01565

Parcel: 12904157A

Inspection Status: Approved

Inspection History: MECHANICAL - PROGRESS

Permit Number - T08CM01565

Inspection Description - MECHANICAL - PROGRESS

Inspection Status - Approved

Date Description Inspector Results Comments
08/06/2010 MECHANICAL - PROGRESS Approved IVRS - Inspection :*
04/20/2010 MECHANICAL - PROGRESS Partial Approval IVRS - Inspection :*
1) DUCT AND RELATED ITEMS IN ROOMS OK TO COVER BOTH FLOORS
2) RECEIVED CHECK #10628 IN THE AMOUNT OF $150.00 FOR AFTER HRS INSPECTION
04/19/2010 MECHANICAL - PROGRESS Denied 1) CONDENSATE PIPING STILL DOES NOT HAVE PROPER FALL, THIS IS THE THIRD TIME I HAVE LOOKED AT THIS, STILL NO RESULTS, HAVE MECHANICAL CONTRACTOR ON SITE AND AVAILABLE FOR NEXT INSPECTION, ANY FURTHER FAILURES ON THIS WILL RESULT IN A REFEE