Permit: T08CM01565

Parcel: 12904157A

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
03/18/2010 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
1) PEX OK
2) PVC OK
3) FLANGES OK
03/15/2010 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) STOPPED INSPECTION AFTER 1ST FLOOR
2) THE FIRST EIGHT FEET OF HOT AND COLD WATER PIPING TO BE INSULATED AT THE WATER HEATER
3) AT STAND PIPE RECEPTORS-TRAP ARM TO BE AT LEAST TWO PIPE DIAMETERS IN LENGTH
4) PLUMBERS TAPE NOT A LISTED STRAP
5) CORRECT BACK PITCHED SECTIONS