Permit: T08CM01385

Parcel: 137055310

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
07/07/2009 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
1) OK GAS TILES IN KITCHEN AREA
07/01/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) DINING AREA OK FOR TILES
2) SECOND LAYER OF FIRE WRAP OK
05/07/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK TO INSULATE DUCT FRONT AREA
05/04/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
05/01/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. PLANS SHOW BELL TAPS, STRAIGHT TAPS ARE INSTALLED
2. SEAL ALL DUCT JOINTS WITH SEALER
3. CONDENSATE PIPING NOT PER PLANS, INSULATE PIPING ABOVE CEILING OR IN WALLS
4. ALL TYPE 1 HOODS MUST BE A MIN. OF 18" TO ALL COMBUSTIBLE MATERIAL (NO WOOD STUDS IN WALL)