Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
Permit Number - T08CM01385
Inspection Description - PLUMBING - ROUGH, SOIL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/19/2009 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection :* | |
05/15/2009 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection :* PROVIDE VENT FOR FLOOR DRAIN FD-3 |
|
03/30/2009 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* GREASE INTERCEPTOR TEST OK |
|
03/23/2009 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* INSIDE SLAB ROUGH SOIL OK |
|
03/20/2009 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* IN BAR LOCATION 3" FS's REQUIRE 3" CLEANOUTS OTHER LOCATIONS OK TO COVER - SUPPORT TRAP ARMS. |
|
03/17/2009 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. POST ADDRESS 2. PROVIDE MATERIAL SPECIFICATIONS 3. CHECK YOUR PIPE SIZING IN WALL AREAS 4. SEVERAL LOCATIONS ARE SIZED WRONG 5. INSTALL PER APPROVED PLANS 6. SINKS REQUIRE CLEANOUTS 7. CHECK SLOPE, ANYTHING LESS THAN 1/4" REQUIRES ENGINEER APPROVAL |