Permit: T08CM01385

Parcel: 137055310

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Permit Number - T08CM01385

Inspection Description - PLUMBING - ROUGH, SOIL

Inspection Status - Approved

Date Description Inspector Results Comments
05/19/2009 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
05/15/2009 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
PROVIDE VENT FOR FLOOR DRAIN FD-3
03/30/2009 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
GREASE INTERCEPTOR TEST OK
03/23/2009 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
INSIDE SLAB ROUGH SOIL OK
03/20/2009 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
IN BAR LOCATION 3" FS's REQUIRE 3" CLEANOUTS
OTHER LOCATIONS OK TO COVER - SUPPORT TRAP ARMS.
03/17/2009 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. POST ADDRESS
2. PROVIDE MATERIAL SPECIFICATIONS
3. CHECK YOUR PIPE SIZING IN WALL AREAS
4. SEVERAL LOCATIONS ARE SIZED WRONG
5. INSTALL PER APPROVED PLANS
6. SINKS REQUIRE CLEANOUTS
7. CHECK SLOPE, ANYTHING LESS THAN 1/4" REQUIRES ENGINEER APPROVAL