Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T08CM01385
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/24/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) SUPPORT VDV CABELING 725.24 AND 300.11 6' INTERVALS UP OFF OF GRID AND INDEPENDENT |
|
07/22/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
07/17/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
07/17/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) NEED ARC SHIELDS AT COMBUSTIBLES 314.20 & 314.21 2) NEED ENGINEER CERTIFICATION FOR OUTDOOR LIGHTING 3) FINISH VDV-MUZAC 4) PANEL DIRECTORIES PER 408.4 5) EM LIGHTS TO BE PER 700.12 (F) 6) WALK-IN FAU COILS NEED DISCONNECTING MEANS 7) RACE WAY AT WALK-IN TO BE SEALED PER 300.7 8) MISSING FIXTURE BEER COOLER |
|
07/16/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* |