Permit: T08CM01385

Parcel: 137055310

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T08CM01385

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
07/24/2009 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
07/01/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) BOND GAS PIPING
2) EQUIPMENT GROUNDING CONDUCTOR FROM SES TO MDP NOT SIZED PROPERLY, SIZE PER NEC 250.122
3) OK DROP CEILINGS
4) RECEIVED LETTER OF TORQUE
5) RECALL FOR 7/2/09 TO SEE NEW EQUIPMENT GROUNDS
05/29/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK VDV CABLING IN SOFFITS
05/26/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK CANS VESTIBULE, BAR, WAITING, BAR DINING AND PRIVATE DINING - OK LID MANAGERS OFFICE, CLOSET

1. FINISH VDV CABLING THESE AREAS
05/19/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
05/14/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) OK CANS AND LIGHTS PERIMETER SOFFITS DINING
2) OK FRONT TOWER (UP) LIGHTING