Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T08CM01385
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/24/2009 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
07/01/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) BOND GAS PIPING 2) EQUIPMENT GROUNDING CONDUCTOR FROM SES TO MDP NOT SIZED PROPERLY, SIZE PER NEC 250.122 3) OK DROP CEILINGS 4) RECEIVED LETTER OF TORQUE 5) RECALL FOR 7/2/09 TO SEE NEW EQUIPMENT GROUNDS |
|
05/29/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK VDV CABLING IN SOFFITS |
|
05/26/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK CANS VESTIBULE, BAR, WAITING, BAR DINING AND PRIVATE DINING - OK LID MANAGERS OFFICE, CLOSET 1. FINISH VDV CABLING THESE AREAS |
|
05/19/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
05/14/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) OK CANS AND LIGHTS PERIMETER SOFFITS DINING 2) OK FRONT TOWER (UP) LIGHTING |