| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/23/2009 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection :* 1) NO BOND REQUIRED 2) NOTE: CONTR TO INSURE THAT ONLY AUTHORIZED PERSONS TO HAVE ACCESS TO ELECTRICAL EQUIPMENT ALL RECEPTS FOR CONST. USE TO BE GFI PROTECTED |
|
| 04/22/2009 | ELECTRIC - CABLE DROP | Partial Approval | IVRS - Inspection :* 1. RECEIVED LETTER FROM MCGETRIC FOR SERVICE MODIFICATIONS 400 AMP CT AND DISC. SW. IN LIEU OF SWITCHBOARD 2. INSTALL BUSHINGS ON CONDUITS ENTERING MAIN PANEL MDP FROM U.G. 352.46 - 300.5 NEC 3. BOND NEUTRAL IN SERVICE DISCONNECT |
|
| 04/09/2009 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL R-PINS AT SERVICE DISC. SW. 2. MAIN BOND JUMPER IN SERVICE MAIN DISC. SW. 3. REVISE PLAN TO SHOW CT CAN AND 400A DISCONNECT SW IN LIEU OF SWITCH BOARD |
|
| 02/19/2009 | ELECTRIC - CABLE DROP | Partial Approval | IVRS - Inspection :* OK REMAINDER OF SECONDARY CONDUIT TO TEP X-FORMER |
|
| 01/22/2009 | ELECTRIC - CABLE DROP | Partial Approval | IVRS - Inspection :* 1. OK 2 - 3" PVC 20' FROM TEP XFMR TO SES FOR STAPLES 2. OK 3 - 4" PVC 20' FROM TEP XFMR TO BUILDING FOR RAINBOW 3. OK 4 -4" PVC 20' FROM TEP XFMR HEADING SOUTH 100' FOR ROSS 4. INSTALL WARNING RIBBON PER NEC 300.5 |
|
| 01/21/2009 | ELECTRIC - CABLE DROP | Not ready for Inspection | IVRS - Inspection :* |