Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T08CM00821
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/03/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
07/02/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* WILL RESCHEDULE |
|
05/29/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PARTIAL INSPECTION - SPACE NOT TO BE OCCUPIED BEFORE APPROVAL 1. LOADS TO ORIGINATE FROM PANELS AS SHOWN ON APPROVED PLANS 2. PANEL DIRECTORIES TO BE CORRECT - GO TO WHAT THEY SAY 3. EMERGENCY LIGHTING NOT PER PLAN 4. PLANS SHOW 200 AMP BUS PANEL "B"? 5. FINISH ALL PREVIOUS CORRECTIONS |
|
05/28/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. NEED TO TAKE OUT PERMIT FOR NEW SIGN BEFORE INSPECTIONS CONTINUE 2. OTHER CORRECTIONS IN PROGRESS 3. NEED PERMIT FOR NEW AC |
|
05/23/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SIGNS TO BE LISTED 2. NEED DISCONNECT FOR SIGNS 3. SIGNS TO HAVE MANUFACTURES NAME PLATE 4. PLAN CALLS FOR OCCUPANCY SENSORS 5. DISCONNECT ON ROOF ONLY RATED FOR 30 AMP NEEDS TO BE RATED FOR 60 AMP. SEE RATING OF UNIT. 6. NEED ROOFTOP GFI RECEPTACLE FOR SERVICING AC UNITS 7. INSTALL PROTECTIVE BUSHING ON FEEDER TO PANEL B 8. INSTALL PANEL DIRECTORIES |