Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/03/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 04/17/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* CORRECTIONS NOT COMPLETED NEED TO PAY REINSPECTION FEE DO NOT CALL BEFORE ALL COMPLETE |
|
| 04/16/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* IN CEILING 1. WIRE NUTS TO BE USED AS LISTED 2. INSTALL K.O'S AS NEEDED 3. PLANS AND DISCONNECTS AND NEW CKT FOR WATER HEATERS 4. FAN BOXES (LISTED) FOR CEILING FANS 5. DEMO ALL ABANDONED/UNUSED WIRING & EQUIPMENT 6. HAVE OVERFILLED J-BOXES 7. ALL FIXTURES TO HAVE SUPPORT WIRES 8. EMERGENCY LIGHTING TO BE PER NEC 700.12(F) ALSO PER PLAN 9. CORD REELS TO BE USED AS LISTED, NOT TO BE ABOVE CEILING WALLS 1. PLAN CALLS FOR NEW PANEL "B" 2. ALSO CALLS FOR BOTH RECETACLES 3. NAIL PLATES NEEDED WHERE HOLE 1 1/4 OR LESS FROM STUD FACE OK TO COVER U.G RACEWAYS TO SALES COUNTER OK TO DRYWALL NEW FRAMED WALLS |