Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/25/2009 | ELECTRIC - INTERMEDIATE | Approved | ||
| 08/14/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK EMT IN CHASE MAIN FLOOR |
|
| 08/07/2008 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) PROPERLY SUPPORT CONDUIT IN CHASE 2) WAITING ON INFO FROM STANTEC ON CONDUITS 3) 300.19 MAY APPLY |
|
| 07/07/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. PROVIDE COPY OF SATISFACTORY TEST RESULTS OF GENERATOR SYSTEM 2. VERIFY LISTING OF UNIT AS PER CODE & PLANS |
|
| 06/26/2008 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* NO WORK BEING COVERED, NO INSPECTION AT THIS TIME |