Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/25/2009 | ELECTRIC - UNDERGROUND | Approved | ||
| 04/23/2008 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection : See detailed listing on site.| 999* INSPECTION FOR GENERATOR PAD GROUNDING ELECTRODE FOR GENERATOR TO MEET THE REQUIREMENTS OF NEC 250.52 REBAR IN SLAB DOES NOT MEET ANY OF THE DEFINITIONS A GROUNDING ELECTRODE. RECOMMEND DRIVING GROUND ROD AS SHOWN ON APPROVED PLAN. |