Permit: T08CM00671

Parcel: 11004343C

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
04/17/2009 PLUMBING - FINAL Approved IVRS - Inspection :*
04/16/2009 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
04/06/2009 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. PROVIDE STERILIZATION OF DOMESTIC WATER SYSTEM INCLUDING YARD PIPING DOWN STREAM OF RP - UPC 609
2. PROVIDE INTERNAL BACKFLOW CERT
3. WATER HAMMER AT INTERNAL BACKFLOW CERT
4. BREAKROOM SINK & DW NOT COMPLETE
5. CLIP ALL SIDES OF ALL SINKS
6. ONLY ONE SLIP NUT ALLOWED DOWN STREAM OF P-TRAP
7. CAULK ALL FIXTURES
8. EXPOSE CLEANOUTS
9. PROVIDE CORRECT PLUGS AND SEAL ALL THREADED PLUGS
10. KINK ON LAV, ALSO, TEST LAVS W/BUCKET
11. WH PIPING NOT PER DETAIL