Permit: T08CM00671

Parcel: 11004343C

Inspection Status: Approved

Inspection History: PLUMBING - YARD WTR LINE/TEST

Date Description Inspector Results Comments
01/12/2009 PLUMBING - YARD WTR LINE/TEST Approved IVRS - Inspection :*
01/09/2009 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection :*
SECURE TRACER WIRE TO RISER
12/30/2008 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection :*
1) YARD LINE FROM METER THRU RP TO BLDG IS SCHEDULE 40 PVC. SPEC BOOK 15100 2.04 C SPECIFIES CLASS 200 OR 14 PVC. 100 PSI TEST IS OK
REDLINE LOCATION RP, PROVIDE SUPPORT PER TUCSON WATER DETAIL
RECALL FOR INSPECTION OF BLDG CONNECTION
12/23/2008 PLUMBING - YARD WTR LINE/TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
NEVER TEST PLASTIC W/AIR