Permit: T08CM00660

Parcel: 11623063C


Addresses:

960 S FREEWAY

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
08/08/2008 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
07/24/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO COVER WALLS
RECALL FOR CLOSET FLANGES AND SHOWER PAN LINERS
07/23/2008 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
PROVIDE APPROVED PLANS
INSTALL SAFETY PLATES AT BASE PLATE
RM. 144 SHOWER TRAP ARM OF UPSTAIRS SHOWER IS CRACKED. REPLACE DAMAGED PIPE.
INSTALL PROPER TRANSITION BANDS IN ALL LOCATIONS

SECURE COPPER STUB OUTS
KEEP OPEN DRAIN PIPES CAPPED

TEST ON TUBS OK
SHOWER PAN LINER CODE ILLUSTRATIONS PROVIDED
CALL FOR INSP. OF LINER AND CLOSET FLANGES WHEN READY