Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/27/2008 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 08/26/2008 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* ROOF JACKS NOT SEALED KITCHEN E.F NOT PROPERLY INSTALLED 1. EF-2 & 3 NOT PROPERLY SIZED 2. PROVIDE SEDIMENT TRAPS AT KITCHEN GAS PIPING 3. WATER HEATER FLUE MUST BE DOUBLE WALL THROUGH CEILING 4. PROVIDE 1" MIN. CLEARANCE TO COMBUSTIBLES ON B-VENT 5. SEAL ALL OPENINGS IN WALL FLASHING 6. PROVIDE BIRD SCREEN AT EXHAUST JACKS 7. PROVIDE ROOF JACKS AT CONDENSATE AND WATER PIPING |