Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/27/2008 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 07/29/2008 | MECHANICAL - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. MUA DUCT NOT SUPPORTED PER PLANS/DETAIL 108 2. MUA DUCT NOT SEALED 3. WATER HEATER FLUE PIPING NOT INSTALLED 4. RESTROOM EXHAUST FANS NOT INSTALLED 5. FLEX DUCT NOT INSTALLED PER DETAIL 109 |