Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T08CM00643
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/29/2008 | PLUMBING - FINAL | Approved | ||
08/28/2008 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* CO PLUGS OK VENTS OK WALL BRACKET FOR LAV OK PER VINCE CATALANO INSTALL BACKFLOW ASSEMBLY IN ACCESSIBLE LOCATION BELOW 5' HARD PIPE UPSTREAM SIDE. PROVIDE CERT. SERVICE ICE BIN DRAIN TO WALL AT FS DRIPS ON BEV. DISP. CONNECTION |
|
08/27/2008 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. CORRECT VENT TERMINATION WITHIN 10' OF RTU AIR INTAKE. 2. PAINT ABS VENT TERMINATIONS. 3. PROVIDE DOCUMENTATION FOR CHANGES TO PLAN SPECS, IE. FLOOR MOUNTED LAV CARRIERS. 4. PROVIDE BACKFLOW PROTECTION AT ICE MACHINE 5. CERTS RECEIVED FOR BEV. EQUIPMENT 6. PROVIDE A CLEAN WATER REPORT PER SPEC 24 7. CORRECT DAMAGED T&P AND PIPE SEPARATELY TO TERMINATION 8. SEPARATE, TRAP AND PROPERLY INSTALL ID WASTE AT ICE MACHINE 9. CORRECT DRAINS FROM BEV. DISP. USE PVC PRIMER SUPPORT 10. SUPPORT LAV MV's 11. PROVIDE CLEANOUT PLUGS WITH A FACTORY TAP TO RECEIVE MACHINE SCREW. 12. LEAVE COVER PLATES OFF FOR INSP. |