Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T08CM00643
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/01/2008 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* FLANGES OK |
|
07/30/2008 | PLUMBING - INTERMEDIATE | Not ready for Inspection | BOWLS SET W/O INSPECTION CONTINUED "NOT READY" WILL RESULT IN REINSPECTION FEE |
|
06/11/2008 | PLUMBING - INTERMEDIATE | Partial Approval | 1. OK TO COVER ALL AREAS GAS PRESSURE TEST OK 2. NOTE: CLOSET FLANGES TO EXTEND 1/4" ABOVE FINISHED FLOOR |
|
06/09/2008 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. ABS IS TO BE SUPPORTED AT EACH CHANGE OF DIRECTION OR ELEVATION AND AT THE ENDS OF BRANCHES, THEN NO MORE THAN FOUR FEET BETWEEN HANGERS 2. VERTICAL PIPING IS TO BE SUPPORTED 3. INSULATE WATER PIPING PER 2006 IECC 4. USE APPROVED HANGERS AND SUPPORTS 5. BUSHINGS ON GAS PIPING NOT PERMITTED IN INACCESSIBLE LOCATIONS 6. PIPING MAY BE SUPPORTED TO THE WALL, BUT NOT BY THE WALL |