Permit: T08CM00643

Parcel: 10602001C


Addresses:

3984 N ORACLE RD


Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Permit Number - T08CM00643

Inspection Description - PLUMBING - ROUGH, SOIL

Inspection Status - Approved

Date Description Inspector Results Comments
06/04/2008 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
OK TO COVER UNDERGROUND
OK TO COVER INTERCEPTOR
OK TO COVER SEWER CONNECTION TO P.O.C
06/02/2008 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1. OK TO POUR INSIDE
2. VENT FITTINGS ARE TO OPEN IN THE DIRECTION OF FLOW
YOU MAY COVER THE REST.
05/30/2008 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1. PROVIDE APPROVED HEALTH DEPT. PLAN -- HAND SINK LOCATION ARE DETERMINED BY THEM
2. OK TO COVER, SUBJECT TO HEALTH DEPT APPROVAL OF RELOCATION
3. CALL 03005 FOR PRE-POUR
05/28/2008 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. VERTICAL X HORIZONTAL CHANGE OF DIRECTION TO BE A SWEEP
2. VENT THE FIXTURE TRAP NOT THE DRAIN LINE
3. WHERE A VENT CONNECTS TO A HORIZONTAL DRAIN IT SHALL HAVE ITS INVERT TAKEN OFF ABOVE THE DRAINAGE CENTER LINE DOWNSTREAM OF THE TRAP BEING SERVED
4. CONTRACTOR TO PAY A REINSPECTION FEE
05/27/2008 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
1. CONTINUED "NOT READY" WILL RESULT IN A
REINSPECTION FEE
2. EACH FIXTURE TRAP TO HAVE A CONNECTING VENT DOWNSTREAM OF THE TRAP BEING SERVED
3. HORIZONTAL VENTING BELOW FLOOD RIM ONLY PERMITTED FOR STRUCTURAL CONDITIONS
4. NO HUB BAND NOT PERMITTED ON ABS
5. NOTE: AT GREASE INTERCEPTOR, ABS AND PVC MAY NOT BE INTERMINGLED.
05/23/2008 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. REDLINE CHANGES PRIOR TO INSP.
2. FULL SIZE CO's NEEDED
3. VENT TAKE-OFF SHALL BE ABV. FLOW LINE 45 DEG. MIN.
4. ALL FIXTURES REQUIRE A VENT SHADE,
PROVIDE 1/4" SLOPE