Permit: T08CM00643

Parcel: 10602001C


Addresses:

3984 N ORACLE RD


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T08CM00643

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/28/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
UNLISTED HORCHATA MACHINE IS NOT TO BE PLUGGED INTO EQUIPMENT IF INSTALLED TO BE LISTED

SERVICE EQUIPMENT WAS APPROVED BY DAN SANTA CRUZ
08/27/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. FINISH PANEL DIRECTORY
2. HORCHATA MACHINE UNLISTED
08/26/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. SUPPORT M/C CABLES
2. PANEL DIRECTORY TO BE AS PER 408.4
NO ABBREVIATIONS AND LEGIBLE
3. HORCHATA MACHINE: MOVE SO SWITCH IS ACCESSIBLE AND VERIFY LISTING
4. FINISH #4 & 5 OF INSPECTION ON 7/29/08
07/29/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. BOXES MORE THAN 1/4" FROM BOX TO SURFACE - 314.20
2. BOX OVERFILLED
3. FINISH ANSUL WIRING
4. NEED KITCHEN EQUIPMENT TO VERIFY LISTINGS
5. FINISH WALK IN BOX AND SEAL CONDUIT AS PER 300.7
6. A PERMANENT CIRCUIT DIRECTORY AS PER 408.4
7. SUPPORT VDV CABLING UP OFF OF GRID - 725.24
8. PLEASE HAVE ELECTRICIAN OPEN SERVICE & PANELS TO INSPECT