Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T08CM00643
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/28/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* UNLISTED HORCHATA MACHINE IS NOT TO BE PLUGGED INTO EQUIPMENT IF INSTALLED TO BE LISTED SERVICE EQUIPMENT WAS APPROVED BY DAN SANTA CRUZ |
|
08/27/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. FINISH PANEL DIRECTORY 2. HORCHATA MACHINE UNLISTED |
|
08/26/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. SUPPORT M/C CABLES 2. PANEL DIRECTORY TO BE AS PER 408.4 NO ABBREVIATIONS AND LEGIBLE 3. HORCHATA MACHINE: MOVE SO SWITCH IS ACCESSIBLE AND VERIFY LISTING 4. FINISH #4 & 5 OF INSPECTION ON 7/29/08 |
|
07/29/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. BOXES MORE THAN 1/4" FROM BOX TO SURFACE - 314.20 2. BOX OVERFILLED 3. FINISH ANSUL WIRING 4. NEED KITCHEN EQUIPMENT TO VERIFY LISTINGS 5. FINISH WALK IN BOX AND SEAL CONDUIT AS PER 300.7 6. A PERMANENT CIRCUIT DIRECTORY AS PER 408.4 7. SUPPORT VDV CABLING UP OFF OF GRID - 725.24 8. PLEASE HAVE ELECTRICIAN OPEN SERVICE & PANELS TO INSPECT |