Permit: T08CM00643

Parcel: 10602001C


Addresses:

3984 N ORACLE RD


Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Permit Number - T08CM00643

Inspection Description - ELECTRIC - SERVICE UPGRADE

Inspection Status - Approved

Date Description Inspector Results Comments
08/28/2008 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
07/30/2008 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :*
1. SEE NOTES 1, 2, 3, 4, 5, 6, 7
2. OK SERVICE EQUIPMENT, EXCEPT DISC. SW. NEED R-PINS
3. EM LIGHTING OK
4. 110V KITCHEN RECEPTS NEED TO BE GFI PROTECTED
PER 210 NEC
07/02/2008 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :*
07/01/2008 ELECTRIC - SERVICE UPGRADE Not ready for Inspection IVRS - Inspection :*
DAN SANTA CRUZ TO COMPLETE INSPECTION 909-5173
THIRD ST ELECTRIC ROC 222192
06/25/2008 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. ALL EQUIPMENT TO BE OPEN FOR INSPECTION THIS INCLUDES METER & GUTTER
2. DISCONNECT FOR SERVICE MOUNTED TO HIGH - NEC 404.8
3. CANNOT USE SHEETMETAL SCREW FOR GROUND CONNECTION -- NEC 250.8
4. MARK "SERVICE DISCONNECT" - NEC 230.70
5. LOCK NUTS TO BE WRENCH TIGHT
6. INSTALL SEALING WASHERS FOR WEATHER PROOFING OF CONNECTIONS
7. INSTALL GASKET @ LB
8. BONDING OF BAS AND WATER TO PER NEC 250
06/17/2008 ELECTRIC - SERVICE UPGRADE Partial Approval 1) CONTRACTOR REQUEST BEFORE HOURS INSP PAID $150 CHECK #7059
2) PANEL FEEDERS NOT INSTALLED YET
3) DO NOT ENERGIZE INSIDE PANEL PRIOR TO INSPECTORS APPROVAL