Permit: T08CM00587

Parcel: 122184340


Addresses:

3501 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: PLUMBING - YARD WTR LINE/TEST

Date Description Inspector Results Comments
08/14/2009 PLUMBING - YARD WTR LINE/TEST Approved IVRS - Inspection :*
1) POST ADDRESS
2) 2 1/2" PVC YARDWATER INSTALLED OK
3) OK TO COVER
08/06/2009 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection :*
1) 2" PVC AND GALVANIZED INSTALLED
2) OK TO COVER SUBJECT TO ENGINEERS CLARIFICATIONS
3) PLAN DISCREPANCY; SITE UTILITY PLAN SPECIFIES 2" YARD WATER BUT P-1 SPECIFIES 2 1/2" RP AND DOMESTIC SERVICE INTO BLDG (REVISION TO INSTALL 2" WOULD BE REQUIRED)
4) MP1 SPECIFIES COPPER AND PVC. PROVIDE APPROVAL FROM ENGINEER FOR MATERIAL SPEC AND RP SIZE
08/05/2009 PLUMBING - YARD WTR LINE/TEST Not ready for Inspection IVRS - Inspection :*
1) NO ONE ON SITE AT 1:45 PM. COURTESY CALL PROVIDED AT 1 PM
2) NEED TO SEE PLANS AND MATERIAL SPECS
3) IS GALVANIZED PIPE APPROVED PER YOUR ENGINEERS SPECS ?
4) PROVIDE TEST, METER IS OFF
07/28/2009 PLUMBING - YARD WTR LINE/TEST Not ready for Inspection IVRS - Inspection :*
1) MET WITH MIKE (CHESTNUT) AND LARRY (DESERT EARTH) 4" DIP INSTALLATION FOR SEWER PVC SCHEDULE 40 FOR WATER WITH TEST IN PLACE AT TIME OF INSPECTION
2) SEWER REQUIRES LONG RADIUS FITTINGS PER 2006 UPC