Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - YARD WTR LINE/TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/14/2009 | PLUMBING - YARD WTR LINE/TEST | Approved | IVRS - Inspection :* 1) POST ADDRESS 2) 2 1/2" PVC YARDWATER INSTALLED OK 3) OK TO COVER |
|
| 08/06/2009 | PLUMBING - YARD WTR LINE/TEST | Partial Approval | IVRS - Inspection :* 1) 2" PVC AND GALVANIZED INSTALLED 2) OK TO COVER SUBJECT TO ENGINEERS CLARIFICATIONS 3) PLAN DISCREPANCY; SITE UTILITY PLAN SPECIFIES 2" YARD WATER BUT P-1 SPECIFIES 2 1/2" RP AND DOMESTIC SERVICE INTO BLDG (REVISION TO INSTALL 2" WOULD BE REQUIRED) 4) MP1 SPECIFIES COPPER AND PVC. PROVIDE APPROVAL FROM ENGINEER FOR MATERIAL SPEC AND RP SIZE |
|
| 08/05/2009 | PLUMBING - YARD WTR LINE/TEST | Not ready for Inspection | IVRS - Inspection :* 1) NO ONE ON SITE AT 1:45 PM. COURTESY CALL PROVIDED AT 1 PM 2) NEED TO SEE PLANS AND MATERIAL SPECS 3) IS GALVANIZED PIPE APPROVED PER YOUR ENGINEERS SPECS ? 4) PROVIDE TEST, METER IS OFF |
|
| 07/28/2009 | PLUMBING - YARD WTR LINE/TEST | Not ready for Inspection | IVRS - Inspection :* 1) MET WITH MIKE (CHESTNUT) AND LARRY (DESERT EARTH) 4" DIP INSTALLATION FOR SEWER PVC SCHEDULE 40 FOR WATER WITH TEST IN PLACE AT TIME OF INSPECTION 2) SEWER REQUIRES LONG RADIUS FITTINGS PER 2006 UPC |