Permit: T08CM00514

Parcel: 10511061R


Addresses:

4500 N ORACLE RD


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T08CM00514

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/16/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/02/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK ELECTRICAL, FIRE ALARM NOT INSTALLED YET
03/27/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
LAST ITEM FINISH A/C's
RECEIVED GENERATOR REPORT
03/25/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. PANEL DIRECTORIES TO BE 408.4
2. PROPERLY GROUND TRANS PER SWITCH
3. NEED GENERATOR REPORT
4. LABEL PANEL COVERS PER 210.5
ALSO, CORRECTLY IDENTIFY GROUNDED CONDUCTORS
AS DISCUSSED
5. NO MORE THAN 360 DEG. IN CONDUIT RUNS
6. LABEL DISCONNECT
7. FINISH A/C's