Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/16/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 04/02/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK ELECTRICAL, FIRE ALARM NOT INSTALLED YET |
|
| 03/27/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* LAST ITEM FINISH A/C's RECEIVED GENERATOR REPORT |
|
| 03/25/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. PANEL DIRECTORIES TO BE 408.4 2. PROPERLY GROUND TRANS PER SWITCH 3. NEED GENERATOR REPORT 4. LABEL PANEL COVERS PER 210.5 ALSO, CORRECTLY IDENTIFY GROUNDED CONDUCTORS AS DISCUSSED 5. NO MORE THAN 360 DEG. IN CONDUIT RUNS 6. LABEL DISCONNECT 7. FINISH A/C's |