Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T08CM00514
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/16/2009 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
03/27/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
03/25/2009 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
|
12/18/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) PLEASE VERIFY RESISTANCE OF GROUNDING ELECTRODE PER 250.56 |
|
12/16/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. INSTALL GROUNDING ELECTRODE SYSTEM FOR TRANSFORMER -- 250.24 2. DISCONNECTING MEANS PER 225.31 & 32 3. NEED ILLUMINATION AT PANELS 110.26 4. NEED GENERATOR LABELING PER 702.8(A) & (B) |
|
12/04/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* BELL END 352.46 & 300.4 |