Permit: T08CM00262

Parcel: 12606204A

Inspection Status: Approved

Inspection History: FIRE SPKLR - FINAL

Date Description Inspector Results Comments
04/23/2009 FIRE SPKLR - FINAL Approved
11/06/2008 FIRE SPKLR - FINAL Partial Approval Phase#4 room 120
Adjust sprinkler heads to 1 inch below drop ceciling
09/16/2008 FIRE SPKLR - FINAL Partial Approval Phase 3 Approved
08/11/2008 FIRE SPKLR - FINAL Partial Approval Phase #3 Rm. 103 Approved, still need to remove plastic piping used for ventilation above ceiling. Above ceiling is a non-combustible area.
08/05/2008 FIRE SPKLR - FINAL Partial Approval Phase #5 Northeast wall correct coverage and northwest entrance correct coverage
07/30/2008 FIRE SPKLR - FINAL Partial Approval ROOM #109 APPROVED (SUPER # 481-4745)
07/08/2008 FIRE SPKLR - FINAL Partial Approval Ok for phase 1 only.
Need up to date fire sprinkler inspection done, last inspection on file is 05/11/04. Thsi done yearly.
Need a 5 year alarm check valve inspection done. This is done every 5 years, nothing on file for the last time this was done.
In room #132 need to correct sprinkler coverage. Can not use small room rule head is 11" off wall.