Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/08/2009 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 04/27/2009 | MECHANICAL - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 03/31/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 03/30/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* ROOM 121 OK FOR TILES |
|
| 03/11/2009 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
| 03/10/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK FOR CEILING TILES ROOMS 117, 121 STILL NEED TO SEE CONNECTIONS TO DIFFUSERS ROOM 121 |
|
| 01/28/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 01/27/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* CONFIRMED PRIMER USED OK FOR CEILING TILES ROOM 121A |
|
| 01/23/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* ALL PVC PIPING MUST HAVE PRIME AT JOINTS PRIOR TO GLUED FITTINGS |
|
| 01/14/2009 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
| 01/13/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | OK TO PROCEED WITH GRID CEILING | |
| 10/21/2008 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK FOR CEILING TILES ROOM 120 |
|
| 09/15/2008 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK CEILING TILES ROOMS 110-113 PHASE 3 |
|
| 09/12/2008 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* RMS. 110 THR 113 MICROBIOLOGY LAB REMOVE ALL NYLON STRAPPING, REPLACE WITH SHEETMETAL STRAPS AND SADDLES PER DETAIL (4) M2 |
|
| 09/11/2008 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
| 08/25/2008 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* PHASE 3 ROOM 105 OK FOR CEILING TILES |
|
| 07/28/2008 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* PHASE 5 OK FOR CEILING TILES PHASE 3 PVC NOT ALLOWED IN A RETURN AIR PLENUM USE SHEETMETAL STRAPS TO SUPPORT SUPPLY AND EXHAUST DUCTS |
|
| 07/17/2008 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* RM 109 PHASE II OK TO ROCK LID MECHANICAL ONLY |
|
| 07/15/2008 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
| 06/09/2008 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* EXHAUST DUCT & DIFFUSERS MISSING PHASE 1 CORRIDOR WILL CHECK ON FINAL OK CEILING PHASE 1 & 5 EXHAUST MISSING IN SERVER ROOM |