Permit: T08CM00262

Parcel: 12606204A

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
05/27/2009 PLUMBING - FINAL Approved IVRS - Inspection :*
INSTALLED PER STANTEC APPROVED PLAN
04/02/2009 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
LAB 121 SINK OK
03/31/2009 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
AT SINK CLEANOUT, REMOVE JIM CAP, MAKE CLEANOUT ACCESSIBLE, INSTALL COUNTER SUNK TAPPED PLUG AND REPLACE CHROME COVER WITH A MACHINE SCREW
02/13/2009 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
PER LETTER FROM P.E.T; NO TRAP PRIMER IS REQUIRED DUE TO FREQUENT USE. STILL NEED APPROVED PLAN REVISION
CAP ALL OPEN DRAINS DURING CONSTRUCTION.
02/11/2009 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
1. SINK RM 121A IS OK
HUB DRAIN IS NOT SHOWN ON APPROVED PLAN
2. WHAT IS THE METHOD OF TRAP SEAL PROTECTION FOR HUB DRAIN AND ALSO FS P-7?
01/09/2009 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
REVISION FOR AAV RM. 125 OK
10/31/2008 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
RM. 120 PAS #4 FIXTURES OK
09/22/2008 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
MICRO PHASE 3 OK
09/18/2008 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
CHRIS @ 481-4745

- CORRECT SLOPE ON SINK TRAP ARMS & CONTINUOUS WASTE
- PROVIDE CORRECT CLEANOUT PLUG
- FINAL INSPECTIONS SHALL BE COMPLETE PRIOR TO USING FIXTURES
08/21/2008 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
SINK P-6 IN RM. 125 IS NOT INSTALLED PER PLAN
SINK INSTALLATION OK
PROVIDE A CITY APPROVED PLAN REVISION AS
REQUESTED ON 7/24
08/11/2008 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
RM. 105 PHASE 3 SINK & EYE WASH OK
07/23/2008 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
CHRIS 481-4745

SOIL PIPE AT P-6 RM 125 OK
INSTALL FOAM WRAP AND HARD CAPS
REDLINE ANY CHANGES
RM 105 PHASE I FINAL APPROVAL OK
07/22/2008 PLUMBING - FINAL Not ready for Inspection CALLED AS REQUESTED - NO ANSWER
TENANT OCCUPIES SUITES 120 & 200 UNIT # OK