Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/15/2009 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 04/15/2009 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* EYE WASH WATER SUPPLY RM. 120 OK |
|
| 03/04/2009 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 01/09/2009 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* RM. 121 A BELOW FLOOR AND IN WALLS OK PROVIDE APPROVED REVISION AT HUB DRAIN |
|
| 10/07/2008 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 10/03/2008 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* PHASE 4 DEMO AT COL. LINES 3A AND C2 -- OK TO COVER |
|
| 08/19/2008 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 07/24/2008 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* P-6 RM. 125 1. INSTALLED PER REDLINES 2. OK SUBJECT TO PLAN REVIEW 3. AAV WILL ONLY BE ALLOWED IF SPECIFIED ON CITY APPROVED PLANS 4. I WOULD LIKE TO REMIND THE DESIGNER THAT THIS IS A MEDICAL CENTER AND ANY ESCAPE OF SEWER GASES COULD HAVE HEALTH AND LIFE SAFETY CONSEQUENCES. 5. AAV's ARE MECHANICAL DEVICES THAT ARE SUBJECT TO FAILURE -- 1.7% OF AAV's FAIL WHEN "WORKING PROPERLY" DUE TO PRESSURE CHANGES WITHIN A BUILDING 6. PROPER VENTING REQUIREMENTS PER UPC COULD BE OBTAINED WITH SOME EFFORT |
|
| 07/22/2008 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 05/22/2008 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* |