Permit: T08BU02091

Parcel: 11501148E


Addresses:

2381 N 4TH AV


Inspection Status: Approved

Inspection History: GRADING - FINAL

Permit Number - T08BU02091

Inspection Description - GRADING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/06/2010 GRADING - FINAL Approved REVIEWED AS-BUILT DRAWING, AND INSPECTED SITE USING REVISED PLANS. AS-BUILT MEETS WHAT WAS CONSTRUCTED ON SITE
02/25/2010 GRADING - FINAL Continued APPROVED GRADING/SITE PLAN HAS BEEN REVISED TO MATCH WHAT WAS BUILT ON SITE.
12/08/2009 GRADING - FINAL Denied 1) PROVIDE A COPY OF DSMR 2-08.5.1A; DSMR-DS-08-60; AND DSMR 2-08.3.0 FOR INSPECTION AND FOR OUR RECORDS.
2) INSTALL ALL 6" DEPRESSED WATER HARVESTING AREAS SHOWN ON YOUR APPROVED PLANS.
3) ADDITIONAL SIDEWALK SCUPPERS WERE INSTALLED ALONG SOUTH AND EAST ACCESS POINTS NOT SHOWN ON THE APPROVED PLANS.
4) MAIN ACCESS ENTRANCE DRIVEWAY WAS NOT CONSTRUCTED PER THE APPROVED PLANS.
5) ROCK RIP RAP AREAS ALONG NORTH SIDE OF PROJECT WAS NOT CONSTRUCTED PER THE APPROVED PLANS - AREAS NEED TO MEET DIMENSIONS SHOWN ON THE PLANS AND INSTALL FILTER FABRIC UNDERNEATH ROCK.
6) NORTH PERIMETER FENCE MUST BE ELEVATED TO ALLOW FOR STORM WATER SITE DRAINAGE UNDER IT, SEE NOTE #6.
7) INSTALL VERTICAL CURBING WHERE SHOWN ON APPROVED PLANS - EXTRUDED CURBING WAS INSTALLED.