Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: GRADING - FINAL
Permit Number - T08BU02091
Inspection Description - GRADING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/06/2010 | GRADING - FINAL | Approved | REVIEWED AS-BUILT DRAWING, AND INSPECTED SITE USING REVISED PLANS. AS-BUILT MEETS WHAT WAS CONSTRUCTED ON SITE | |
02/25/2010 | GRADING - FINAL | Continued | APPROVED GRADING/SITE PLAN HAS BEEN REVISED TO MATCH WHAT WAS BUILT ON SITE. | |
12/08/2009 | GRADING - FINAL | Denied | 1) PROVIDE A COPY OF DSMR 2-08.5.1A; DSMR-DS-08-60; AND DSMR 2-08.3.0 FOR INSPECTION AND FOR OUR RECORDS. 2) INSTALL ALL 6" DEPRESSED WATER HARVESTING AREAS SHOWN ON YOUR APPROVED PLANS. 3) ADDITIONAL SIDEWALK SCUPPERS WERE INSTALLED ALONG SOUTH AND EAST ACCESS POINTS NOT SHOWN ON THE APPROVED PLANS. 4) MAIN ACCESS ENTRANCE DRIVEWAY WAS NOT CONSTRUCTED PER THE APPROVED PLANS. 5) ROCK RIP RAP AREAS ALONG NORTH SIDE OF PROJECT WAS NOT CONSTRUCTED PER THE APPROVED PLANS - AREAS NEED TO MEET DIMENSIONS SHOWN ON THE PLANS AND INSTALL FILTER FABRIC UNDERNEATH ROCK. 6) NORTH PERIMETER FENCE MUST BE ELEVATED TO ALLOW FOR STORM WATER SITE DRAINAGE UNDER IT, SEE NOTE #6. 7) INSTALL VERTICAL CURBING WHERE SHOWN ON APPROVED PLANS - EXTRUDED CURBING WAS INSTALLED. |