Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - KITCHEN EXH HOOD FINAL
Permit Number - T08BU01580
Inspection Description - FIRE - KITCHEN EXH HOOD FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/28/2009 | FIRE - KITCHEN EXH HOOD FINAL | Approved | ||
04/14/2009 | FIRE - KITCHEN EXH HOOD FINAL | Not ready for Inspection | 1.) Electrical circuit not yet wired to shut -off return air system upon activation of extinguishing system. 2.) Relocate manual pull station to a location that is 10 to 20 feet away from closest hazard. 3.) Relocate "K" type portable extinguisher to a location that is 10 to 30 feet from the closest hazard. |
|
03/06/2009 | FIRE - KITCHEN EXH HOOD FINAL | Cancelled |