Permit: T08BU01580

Parcel: 137053110


Addresses:

5266 S 12TH AV #02


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T08BU01580

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/27/2009 MECHANICAL - FINAL Approved IVRS - Inspection :*
03/06/2009 MECHANICAL - FINAL Cancelled IVRS - RI canceled
03/04/2009 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
PROVIDE SMOKE BOMBS FOR SMOKE CONTAINMENT TEST
ALL ELSE OK
02/17/2009 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
CANCELED
02/05/2009 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
DUCT SIZE OK
02/04/2009 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
2 LAYERS OF DUCT WRAP OK
OK TO INSTALL DUCT
02/03/2009 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
02/02/2009 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
LONG SEAMS NOT OVERLAPPED PROVIDE INSTALL INSTRUCTIONS ON NEXT INSPECTION,
PROCEED WITH 2ND LAYER
01/30/2009 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
LONG SEAM ON GREASE DUCT WELDS OK
01/28/2009 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
11/05/2008 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. EXHAUST FAN IS BOLTED AND MASTIC TO THE ROOF WITH NO MEANS OF CLEANING OR ACCESSING DUCT. ALSO, NO MEANS OF CAPTURING GREASE FROM FAN
2. EXHAUST DUCT DOES NOT APPEAR TO BE 16GA
DUCT TERMINATION MUST BE MINIMUM 18" FROM COMBUSTIBLE MATERIALS
3. EXHAUST FAN BEING ANCHORED TO ROOF DOES NOT PROVIDE A MEANS TO VERIFY DUCT CLEARANCE WITHIN TRUSS SPACE.
09/02/2008 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
PROVIDE ACCESS TO ROOF
PROVIDE DETAILED APPROVED PLANS, SHOWING ALL THREE HOODS AND DESCRIBE ALL WORK BEING DONE.