Permit: T08BU01418

Parcel: 11713069E

Inspection Status: Approved

Inspection History: FIRE - ALARM FINAL

Permit Number - T08BU01418

Inspection Description - FIRE - ALARM FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/30/2009 FIRE - ALARM FINAL Approved
09/17/2009 FIRE - ALARM FINAL Partial Approval NEED AS BUILTS
08/25/2009 FIRE - ALARM FINAL Partial Approval Need phone lines
Need smokes moved as written in 1st inspection
Need 24 hr standby 5min run time
08/24/2009 FIRE - ALARM FINAL Not ready for Inspection
08/20/2009 FIRE - ALARM FINAL Denied Need as builts for changes FACP moved
Two phone lines needed before final
Move smokes 3' away from a/c vent and intakes following numbers 82, 71, 17.
Need to do a 24 hour stand by and 5 min run time on NAC RPS-4 second floor.
Need to finish testing lower levels did not get to them.
Need to test tampers and flows.