Inspection History Details
Inspection Status: Approved
Inspection History: GRADING - TIER REV
Permit Number - T08BU00996
Inspection Description - GRADING - TIER REV
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/16/2010 | GRADING - TIER REV | Approved | ||
04/09/2010 | GRADING - TIER REV | Correction Required | 1) CHANGES TO ROW AND ROW ACCESS, PROVIDE APPROVAL FROM ROW INSPECTOR AND SHOW CHANGES ON APPROVED PLANS. 2) PROVIDE SCUPPERS FOR ALL ROOF DRAINS THAT CROSS SIDEWALKS. 3) THE CROSS SLOPE ON ALL SIDEWALKS CAN NOT EXCEED 2%. 4) THE RUN SLOPE ON ADAAG/ANSI APPROVED SIDE WALKS CAN NOT EXCEED 5%. ANY SLOPES GREATER THAN 5% AND LESS THAN 8.3% ARE CONSIDERED A RAMP AND MUST MEET ALL REQUIREMENTS FOR A RAMP. 5) ALL ADAAG/ANSI APPROVED ACCESS RAMPS WITH A RISE GREATER THAN 6" MUST HAVE RAILING INSTALLED ON BOTH SIDES OF THE RAMP. ANY ADAAG/ANSI APPROVED RAMP RUN THAT RISES MORE THAN 30", REQUIRES A LANDING. 6) PROVIDE AN APPROVED PLAN THAT SHOWS CHANGES/OMMISSION OF THE 60" MIN SCREEN/RETENTION WALL ALONG THE EAST PERIMETER. 7) PROVIDE CLARRIFICATION FROM YOUR ENGINEER OF RECORD ON THE NEED FOR A HEAD WALL AT THE INVERSE OF THE 24" CULVERT PIPE AT THE FAR SW CORNER OF THE SITE. 8) PROVIDE A COPY OF A REVISED GRADING PLAN SHOWING CHANGES MADE TO THE STORM WATER CONVEYANCE SYSTEM INSTALLED ALONG THE WEST SIDE OF THE SITE. RE-INSTALL TEMPORARY STORM WATER CONTROLS ALONG THE EAST PERIMETER OF THE SITE. |