Inspection History Details
Inspection Status: Not ready for Inspection
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/07/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. PROVIDE BONDING OF BUILDING GAS PIPING #4 SOLID COPPER WIRE (2) CLAMPS 2. VENT FROM FURNACE TO BE EXTENDED UP WITH FULL SIZE DOUBLE WALL VENT PIPING TO 3' ABOVE TOP OF COOLER INTAKE WHEN WITHIN 10' OF INTAKE 3. REMOVE DRYWALL FROM LOWER COMBUSTION AIR INTAKE BY DOOR OF WATER HEATER ROOM 4. SUPPORT GAS PIPING TO WATER HEATER |