Inspection History Details
Inspection Status: Denied
Inspection History: PLUMBING - FINAL
Permit Number - T07PL00273
Inspection Description - PLUMBING - FINAL
Inspection Status - Denied
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/15/2007 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* HENRY 275-2431 AGA VALVES REQUIRED AT APPLIANCE SHUT OFFS WATER HEATER IS LEAKING, LEANING AND READY TO FALL THROUGH FLOOR. REPAIR FLOOR SET WH IN PAN. T&P IS NOT PROPERLY TERMINATED COMBUSTION AIR OPENINGS REQUIRED SUPPORT SUSPENDED GAS PIPING FROM STRUCTURE NOT FROM BLOCKS SUPPORTING TRAILER. USE PIPE SUPPORTS TRAILER IS FOR SALE. |
|
| 02/14/2007 | PLUMBING - FINAL | Partial Approval | 1. THIS INSPECTION IS FOR SERVICE PIPING FROM METER TO MOBILE HOME ONLY. 2. MOBILE HOME DOES NOT HAVE A TEST NOR DOES IT MEET CURRENT CODES. THIS APPROVAL DOES NOT MEAN IT IS OK TO RELEASE GAS TO UNIT #48 3. OK TO BACKFILL |
|
| 02/09/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. NO CHANGE FROM LAST INSPECTION 2. PLEASE READ AND COMPLY WITH ALL OF THE NOTES FROM 02/07/07 |
|
| 02/07/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) UNDERGROUND GAS PIPING REQUIRES A MINIMUM OF 18" OF COVER-SEE APPENDIX "E" 2003 UPC E 36.1 AND 1211.1.2 MINIMUM COVER 2) ALL PIPING UNDER M.H. TO BE ADEQUATELY SUPPORTED AND TESTED. ALL VALVES TO BE AGA OR CSA APPROVED 3) WILL NEED TO SEE ALL PIPING ALL CONNECTIONS AND A TEST ON THE ENTIRE SYSTEM |