Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T07PL00273

Parcel: 106120700

Inspection Status: Denied

Inspection History: PLUMBING - FINAL

Permit Number - T07PL00273

Inspection Description - PLUMBING - FINAL

Inspection Status - Denied

Date Description Inspector Results Comments
02/15/2007 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
HENRY 275-2431
AGA VALVES REQUIRED AT APPLIANCE SHUT OFFS
WATER HEATER IS LEAKING, LEANING AND READY TO FALL THROUGH FLOOR. REPAIR FLOOR SET WH IN PAN.
T&P IS NOT PROPERLY TERMINATED
COMBUSTION AIR OPENINGS REQUIRED
SUPPORT SUSPENDED GAS PIPING FROM STRUCTURE NOT FROM BLOCKS SUPPORTING TRAILER. USE PIPE SUPPORTS TRAILER IS FOR SALE.
02/14/2007 PLUMBING - FINAL Partial Approval 1. THIS INSPECTION IS FOR SERVICE PIPING FROM METER TO MOBILE HOME ONLY.
2. MOBILE HOME DOES NOT HAVE A TEST NOR DOES IT MEET CURRENT CODES. THIS APPROVAL DOES NOT MEAN IT IS OK
TO RELEASE GAS TO UNIT #48
3. OK TO BACKFILL
02/09/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. NO CHANGE FROM LAST INSPECTION
2. PLEASE READ AND COMPLY WITH ALL OF THE NOTES
FROM 02/07/07
02/07/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) UNDERGROUND GAS PIPING REQUIRES A MINIMUM OF 18" OF COVER-SEE APPENDIX "E" 2003 UPC E 36.1 AND 1211.1.2 MINIMUM COVER
2) ALL PIPING UNDER M.H. TO BE ADEQUATELY SUPPORTED AND TESTED. ALL VALVES TO BE AGA OR CSA APPROVED
3) WILL NEED TO SEE ALL PIPING ALL CONNECTIONS AND A TEST ON THE ENTIRE SYSTEM