Inspection History Details
Inspection Status: Approved
Inspection History: SIGN ELECTRIC
Permit Number - T07OT01255
Inspection Description - SIGN ELECTRIC
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/18/2008 | SIGN ELECTRIC | Approved | IVRS - Inspection :* | |
09/16/2008 | SIGN ELECTRIC | Not ready for Inspection | IVRS - Inspection :* CANCELED |
|
09/02/2008 | SIGN ELECTRIC | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. FILL OUT MARKING LABELS 2. INSTALL GTO CABLE IN AN APPROVED RACEWAY 3. NEED A WALKWAY PER 600.21 4. A SERVICE LIGHT AS PER 210.70 IS NEEDED |