Inspection Status: Denied
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/06/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. 1/2" GAS LINE NOT ADEQUATE FOR 120,000 BTU 3/4" GAS LINE NOT ADEQUATE 70' FROM METER WITH 40,000 BTU WATER HEATER & 120,000 BTU FURNACE PROVIDE 1" TO FEED FURNACE & WATER HEATER, 3/4 FOR FURNACE & 1/2 FOR WATER HEATER 2. PROVIDE PROPER DESCRIPTION OF WORK & ANY NECESSARY DRAWINGS APPROVED BY CITY OF TUCSON. |
|
| 11/05/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* WRONG PHONE NUMBER NO ONE HOME |