Permit: T07ME00635

Parcel: 111062510


Addresses:

3237 E PATRICIA ST

Inspection Status: Denied

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
09/06/2007 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
- DO NOT SCREW A MALE COPPER FITTING INTO A FEMALE PLASTIC
- THE FITTING IS CRACKED AS A RESULT & LEAKING
- CONDENSATE CANNOT TERMINATE INTO A SEWER VENT
- DO NOT USE WHITE WIRE FOR THE GROUND OR THE HIGH VOLTAGE
- PROPERLY IDENTIFY CONDUCTORS
- PROVIDE A GFI SERVICE RECEPTACLE ON THE ROOF
- NEED TO SEE THE CIRCUIT BREAKER FOR AC UNIT
- MARK THE UNIT DATA PLATE WITH THE PROPER HEAT STRIP INSTALLED & FUSE ACCORDINGLY