Permit: T07ME00504

Parcel: 119034780


Addresses:

718 W 44TH ST

Inspection Status: Denied

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
07/19/2007 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
- PROVIDE AN OVERFLOW SENSOR ON SECONDARY DRAIN.
- EVAP. COIL NOT A MATCH FOR FURNACE
- RELOCATE STAT WIRE FROM TOUCHING FURNACE VENT
- CONDENSATE PUMP HOSE REQUIRES HOSE CLAMPS
- SECURE RECEPTACLE IN WALL
- SECURE WATER LINE IN CLOSET
- DISCONNECT ON ROOF OVERFUSED
- EXTEND FURNACE VENT 3' ABOVE EVAP COOLER
- USE WATER TITE CONNECTORS ON TOP OF CIRCUIT PANEL
- MAINTAIN ADEQUATE CLEARANCE WHEN USING PVC NEAR THE FURNACE VENT CONNECTOR.