Inspection History Details
Inspection Status: Partial Approval
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/19/2007 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1. GAS FLEX CONNECTOR NOT ADEQUATE FOR 100,000 BTU FURNACE. PROVIDE A SEDIMENT TRAP. 2. PROVIDE AN OVERFLOW SENSOR ON SECONDARY DRAIN. 3. DO NOT USE WHITE WIRES FOR THE AC UNIT 4. CONDENSATE CANNOT TERMINATE INTO A SEWER VENT. 5. EXTEND THE FURNACE VENT MIN. 3' ABOVE COMBUSTION AIR INTAKE. |