Permit: T07ME00435

Parcel: 127020480


Addresses:

5372 E 3RD ST

Inspection Status: Partial Approval

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
06/19/2007 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1. GAS FLEX CONNECTOR NOT ADEQUATE FOR 100,000 BTU FURNACE. PROVIDE A SEDIMENT TRAP.
2. PROVIDE AN OVERFLOW SENSOR ON SECONDARY DRAIN.
3. DO NOT USE WHITE WIRES FOR THE AC UNIT
4. CONDENSATE CANNOT TERMINATE INTO A SEWER VENT.
5. EXTEND THE FURNACE VENT MIN. 3' ABOVE COMBUSTION AIR INTAKE.