Permit: T07ME00366

Parcel: 133477360

Inspection Status: Denied

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
06/01/2007 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
VENT PIPE FROM HORIZONTAL UNITS DOES NOT MATCH THE EXISTING VENT SYSTEM. DO NOT USE DIFFERENT MANUFACTURES VENT PIPE & DO NOT CUT THE ENDS TO MAKE THEM FIT.

PERMANENTLY I.D CONDENSORS WITH A MATCHING NUMBER ON THE FAN COIL & AT THE CIRCUIT BREAKERS. THE CIRCUIT FOR THE 2 1/2 TON UNIT IS TOO LARGE.